🇬🇧 Full UI + PDF + National Standard Mapping: UI + PDF in English. Normative references follow international IEC 60364, BS 7671:2018+A2:2022, IEEE, and NFPA 70E/70B.

Field Measurements

Unnamed Project · IEC 60364-4-41 · TN-S · Uo 230 V

BS 7671 Appendix 3 & IEC 60364-6 apply a 0.8× ambient-to-operating temperature factor (Zs_max_site = 0.8 × 0.95 × Uo / Im) plus IEC 60364-5-54 adiabatic PE thermal check. How to calculate Zs & PE (IEC 60364)

Standard Limits, Equations & Space Presets

IEC 60364-4-41 / BS 7671 Maximum Loop Impedance Zs tables for MCBs (Type B/C/D) and fuses, Cmin = 0.95 voltage factor, 0.8x ambient temperature correction, and IEC 60364-5-54 adiabatic PE conductor k factors.

One-Click Normative Presets (Auto-fills Target Limits)

No measurements yet. Tap '+ Circuit' or 'Import CSV / Excel' above to add circuits and evaluate Zs & Ik_min instantly.

Direct MFT import supported: Fluke TruTest / DMS · Megger CertSuite / MFT-X1 · Metrel EuroLink PRO · Chauvin Arnoux · Excel CSV