#05Cable Insulation Resistance & Polarization Index Calculator
Multi-Asset / Multi-Point Equipment Schedule
Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.
Sticker UID: OC-INSU-03D1Standard Limits, Equations & Space Presets
IEEE Std 43-2013 recommended DC test voltages, 40 degC temperature correction factor Kt, minimum insulation resistance R_min, and Polarization Index (PI) / Dielectric Absorption Ratio (DAR) criteria.
Measured Inputs
Calculated / Evaluated Results
PI = R10min / R1min evaluated to IEEE 43-2013 Table 3 (Class A minimum 1.5; Class B, F, H minimum 2.0; any class below 1.0 is a critical degradation alert). DAR = R60s / R30s follows industry field test convention (NETA MTS / Megger guidelines).
Pending / Not tested — results stay neutral until valid measured values are entered.
- Pending
Polarization Index PI = R10min / R1min (Class B, F, H minimum 2.0)
-
Enter R1min and R10min to evaluate the polarization index.
- Pending
DAR = R60s / R30s - Dielectric Absorption Ratio (NETA MTS / Megger Guidelines)
-
Enter R30s and R1min (R60s) to evaluate DAR.
- Pending
IR Corrected to 40 degC (at T = 40.0 degC, V_test = 1,000 V)
- MOhm
R_40C = R_1min x 2^((T - 40)/10); >= 100 MOhm target for power cables / rotating machinery (IEEE 43-2013 §6.3 & §12.2).
Verification Checklist (0 / 13)
1Circuit / machine isolated, locked out (LOTO) and proven dead prior to HV DC injection [IEEE 43 §5]
2Surge arresters, VFDs, electronic meters, and neutral earthing resistors disconnected before testing
3Bushing and cable termination surfaces cleaned and dried to eliminate surface leakage current (Guard terminal used)
4DC test voltage selected per IEEE Std 43 Table 1 (500V <1kV, 1000-2500V MV, 5000V >12kV)
5Winding / conductor temperature and relative humidity (dew-point margin) recorded
6Core-to-earth and phase-to-phase insulation resistance measured for all phase combinations
71-minute IR reading corrected to 40 degC reference using IEEE 43 halving rule Kt = 0.5^((40-T)/10)
810-minute Polarization Index (PI = R10/R1) and 60s/30s DAR recorded (or IEEE 43 §9.2 >5000 MOhm exemption noted)
9Test object grounded for >= 4x test duration after completion to prevent capacitive return-voltage shock
10Cable screen / metallic sheath and armour continuity and single/both-end earthing verified
11Cable terminations, stress cones and boots inspected for corona tracking or partial discharge signs
12Historical IR/PI trend compared against factory/commissioning baseline
13Insulation tester calibration certificate verified and circuit safely restored
General Notes
Free plan: 5 of 5 inspections / calculations left this month.