#02Loop Impedance (Zs) & Breaker Validation Calculator
Multi-Asset / Multi-Point Equipment Schedule
Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.
Sticker UID: OC-LOOP-5B69Standard Limits, Equations & Space Presets
IEC 60364-4-41 / BS 7671 Maximum Loop Impedance Zs tables for MCBs (Type B/C/D) and fuses, Cmin = 0.95 voltage factor, 0.8x ambient temperature correction, and IEC 60364-5-54 adiabatic PE conductor k factors.
Measured Inputs
Uo is synced from project settings (230 V).
Calculated / Evaluated Results
Parametric engine: Zs_limit = (0.95 x Uo) / Im with Cmin = 0.95 (IEC 60364-4-41 / BS 7671), Zs_max_site = 0.8 x Zs_limit for 20 degC ambient testing. Also verifies TT/TN RCD touch voltage (Zs x I_dn <= 50 V) and IEC 60364-5-54 Clause 543.1.2 adiabatic PE conductor thermal withstand S_min = (Ik_min x sqrt(t)) / k.
- Pending
Prospective Earth Fault Current Ik_min = (0.95 x Uo) / Zs
- A
Evaluated for TN-S arrangement at Uo = 230 V.
- Pending
Breaker Magnetic Trip Ratio (Im / In)
-
Not tested - enter the measured value. Acceptance: Im >= In (EN 60898-1: Type B = 5x In, Type C = 10x In, Type D = 20x In) [EN 60898-1 / IEC 60947-2]
- Pending
Overcurrent Magnetic Disconnection (Ik_min >= Im)
-
Enter measured Zs and magnetic trip setting Im to evaluate overcurrent disconnection.
- Pending
Calculated Base Limit Zs_limit = (0.95 x Uo) / Im
- Ohm
Maximum loop impedance at conductor maximum operating temperature.
- Pending
Max Allowable On-Site Limit Zs_max_site (0.8x Temp Corrected)
- Ohm
Zs_max_site = 0.8 x Zs_limit per IEC 60364-6 / BS 7671 Appendix 3 (20 degC ambient test).
- Pending
RCD Touch Voltage & Loop Coordination (No RCD selected)
-
Select an RCD rating IΔn and enter Zs to verify Zs x IΔn <= 50 V (IEC 60364-4-41 §411.5.3).
- Pending
Adiabatic Minimum PE Size S_min = (Ik_min x sqrt(0.4 s)) / 115
- mm2
IEC 60364-5-54 Clause 543.1.2 adiabatic thermal withstand requirement.
- Pending
PE Conductor Thermal Withstand Verification (S_PE >= S_min)
-
Enter Measured Zs and PE Conductor Cross-Section S_PE (mm2) to verify thermal withstand.
Verification Checklist (0 / 12)
1Supply earthing arrangement (TN-S / TN-C-S / TT / IT) and external Ze confirmed at origin [IEC 60364-6 §643.7]
2Protective conductor continuity (R1 + R2) verified end-to-end before live Zs testing
3Polarity verified at distribution board and furthest socket/load point
4No-trip / high-current loop test mode selected appropriately for circuits protected by RCDs
5Measured Zs <= 0.80 x Zs_limit (20 degC ambient correction) or verified against adiabatic heating
6Prospective short-circuit / fault current Ipf <= rated breaking capacity Icn / Icu of protective device
7RCD trip time verified at 1x IΔn (<= 300 ms) and 5x IΔn (<= 40 ms for 30 mA additional protection)
8Protective conductor cross-section S_PE satisfies IEC 60364-5-54 adiabatic equation S_min = Ik·sqrt(t)/k
9No downstream Neutral-to-PE bridge (illegal N-PE bond) present after main equipotential point
10Adjustable MCCB / ACB electronic trip unit dials (Ir, tr, Isd, tsd, Ii, Ig) verified against selectivity study
11Terminations torque-checked and distribution board circuit schedule updated
12MFT loop tester lead nulling and ISO/IEC 17025 calibration validity verified
General Notes
Free plan: 5 of 5 inspections / calculations left this month.