This practical guide shows you how to complete a signed, QR-verified PFC Capacitor Bank Step Current & Detuned Harmonic Reactor Audit certificate in OhmCert Module #28 and how to troubleshoot non-compliant readings on site.
1. Step-by-Step OhmCert UI Workflow
- Open Module #28: Navigate to PFC Capacitor Bank Step Current & Detuned Harmonic Reactor Audit from the Dashboard.
- Load a 1-Click Standard Annex Preset: Open the blue Standard Annex banner at the top and click a preset (such as "50 kVAr / 440 V Step + 7% Detuned Reactor (189 Hz) on 400 V Bus") to populate target limits automatically.
- Enter Your Field Measurements: Fill in the measured inputs (Measured Busbar Line-to-Line Voltage U_L, Capacitor Nameplate Rated Voltage U_CN, Step Nameplate Reactive Power Q_CN (at U_CN), Series Harmonic Detuning Reactor Factor p, System Nominal Frequency f, Measured Step Phase Current I_L1, Measured Step Phase Current I_L2, Measured Step Phase Current I_L3, Detuning Reactor Core / Coil Temperature, Monthly Active Energy Consumption E_active (optional), Monthly Inductive Reactive Energy E_ind (optional), Monthly Capacitive Reactive Energy E_cap (optional)). Blank inputs stay neutral
PENDING. - Complete the 13-Point Checklist: Grade each item, attach photos if needed, and export the SHA-256 signed PDF certificate.
2. Worked Numerical Field Case Study
Scenario: 50 kVAr / 440 V Step + 7% Detuned Reactor (189 Hz) on 400 V Bus (IEC 60831-1 7% Detuned) — Standard industrial detuned step delivering Q_eff = 44.45 kVAr (I_nom = 64.2 A) at 400 V..
- Measured Busbar Line-to-Line Voltage U_L:
400 V - Capacitor Nameplate Rated Voltage U_CN:
440 V - Step Nameplate Reactive Power Q_CN (at U_CN):
50 kVAr - Series Harmonic Detuning Reactor Factor p:
7% (Tuning 189 Hz - Standard Industrial Detuned) - System Nominal Frequency f:
50 Hz - Measured Step Phase Current I_L1:
64.2 A - Measured Step Phase Current I_L2:
63.8 A - Measured Step Phase Current I_L3:
64.5 A - Detuning Reactor Core / Coil Temperature:
78 degC - Monthly Active Energy Consumption E_active (optional):
120000 kWh - Monthly Inductive Reactive Energy E_ind (optional):
14500 kVArh - Monthly Capacitive Reactive Energy E_cap (optional):
8200 kVArh
3. Engineering Troubleshooting: Corrective Actions When a Reading Fails
- Replace any capacitor can whose measured current / capacitance has dropped by more than 10% below expected I_nom or shows top-cap overpressure bulging.
- Replace welded AC-6b contactors or blown HRC fuses causing > 5% 3-phase step current unbalance.
- Add an inductive shunt reactor (SVC) step or fine-grained 2.5-5 kVAr steps if night/weekend LED & UPS loads push capacitive export toward the 15% utility penalty.
→ Try This Worked Example Live in Module #28 (PFC Capacitor & Reactor)