One of the most frequent questions engineers ask before inspecting Emergency Egress & Exit Lighting Test is: "Which standard should I cite on the certificate, and where do the pass/fail limits come from?" This reference guide maps BS 5266 / NFPA 101 to national regulatory adoptions and provides the complete standard annex tables.

1. National & Regional Standard Equivalence Matrix

Region / LanguageAdopted National Standard & Regulatory Code
International / UK (EN)BS 5266 / NFPA 101
Turkey (TR · Türkçe)TS EN 1838 / TS EN 50172 / Binaların Yangından Korunması Yön.
Germany / DACH (DE · Deutsch)DIN EN 1838 / DIN EN 50172 (VDE 0108-100) / ASR A3.4/7
France (FR · Français)NF EN 1838 / NF EN 50172 / NF C 71-800
Spain (ES · Español)UNE-EN 1838 / REBT ITC-BT-28 / CTE DB-SUA 4
Italy (IT · Italiano)UNI EN 1838 / CEI EN 50172 / UNI 11222
Gulf / Middle East (AR · العربية)BS 5266 / NFPA 101 / SASO / DEWA / ADDC

2. Normative Acceptance Criteria & Mathematical Basis

EN 1838 / BS 5266-1 acceptance: escape route centre line >= 1 lx, anti-panic open area >= 0.5 lx, high risk task area >= 10% of the normal level with a 15 lx floor, diversity <= 40:1, and the full rated duration on discharge.

E_high_risk: E_risk_min = max(15 lx, 0.10 x E_normal) — Minimum emergency illuminance for shutting down hazardous processes per EN 1838 §4.4.

3. Official Standard Reference Tables

EN 1838:2013 Emergency Escape Lighting Photometric & Timing Criteria (EN 1838 §4.2 - §4.5)

Emergency Lighting CategoryMin IlluminanceMax Diversity (Emax : Emin)Max Response Time (100% Output)Min Rated Duration
Escape Route (up to 2m wide)>= 1.0 lx on centre line<= 40 : 150% in 5 s, 100% in 60 s1 h (3 h BS 5266 / sleeping risk)
Open (Anti-Panic) Area (> 60 m2)>= 0.5 lx at floor<= 40 : 150% in 5 s, 100% in 60 s1 h (3 h typical)
High-Risk Task Area (Switchgear/Machinery)>= 10% of normal (min 15 lx)<= 10 : 1100% within 0.5 sDuration of hazard (>= 30-60 min)

→ Launch Module #16 with Interactive Standard Annex Tables