One of the most frequent questions engineers ask before inspecting Ex-Proof / ATEX & IECEx Hazardous Area Electrical Inspection is: "Which standard should I cite on the certificate, and where do the pass/fail limits come from?" This reference guide maps IEC 60079-14 / IEC 60079-17 to national regulatory adoptions and provides the complete standard annex tables.

1. National & Regional Standard Equivalence Matrix

Region / LanguageAdopted National Standard & Regulatory Code
International / UK (EN)IEC 60079-14 / IEC 60079-17
Turkey (TR · Türkçe)TS EN 60079-14 / TS EN 60079-17 / ÇSGB Patlayıcı Ortam Yön.
Germany / DACH (DE · Deutsch)DIN EN 60079-14 / 60079-17 (VDE 0165) / BetrSichV
France (FR · Français)NF EN 60079-14 / 60079-17 / Directive ATEX 1999/92/CE
Spain (ES · Español)UNE-EN 60079-14 / REBT ITC-BT-29 / RD 681/2003
Italy (IT · Italiano)CEI EN 60079-14 / 60079-17 (CEI 31-33) / D.Lgs 81/08 Tit. XI
Gulf / Middle East (AR · العربية)IEC 60079-14 / IEC 60079-17 / SASO / DEWA / ADDC

2. Normative Acceptance Criteria & Mathematical Basis

Deterministic ATEX (2014/34/EU) & IEC 60079-14 / 60079-17 compliance engine: verifies Equipment Protection Level (EPL Ga/Gb/Gc & Da/Db/Dc) against Hazardous Zone (0/1/2 & 20/21/22), Gas/Dust Group hierarchy (IIC > IIB > IIA), Temperature Class (T1-T6) vs Auto-Ignition Temperature (AIT), Intrinsic Safety (Ex i) loop parameters (Uo <= Ui, C_cable <= Co), and Ex e motor tE time.

T_surface_max: T_class_max <= T_AIT (Gas) | T_surface <= (2/3) x T_cloud (Dust) — Maximum equipment surface temperature must not exceed the auto-ignition temperature of the explosive atmosphere (IEC 60079-14 §5.6).

Ex_i Loop: Uo <= Ui, Io <= Ii, Po <= Pi, (Ci + C_cable) <= Co, (Li + L_cable) <= Lo — Intrinsic Safety (Ex ia / Ex ib) entity parameter verification between safety barrier and field instrument (IEC 60079-14 §16.2).

3. Official Standard Reference Tables

IEC 60079-14 Table 1 & Table 2: Hazardous Zone, EPL, Gas Group & Temperature Class Matrix (IEC 60079-14 / ATEX Directive 2014/34/EU)

Hazardous ZonePermitted EPLsTypical Protection Concepts (Ex)Gas / Dust Group Hierarchy
Zone 0 (Gas continuous)Ga onlyEx ia, Ex ma, Ex daIIC covers IIB & IIA | IIB covers IIA
Zone 1 (Gas intermittent)Ga or GbEx d (Flameproof), Ex e (Increased Safety), Ex ib, Ex px, Ex mb, Ex qIIC (H2, C2H2) > IIB (C2H4) > IIA (Propane, CH4)
Zone 2 (Gas abnormal)Ga, Gb, or GcEx ec, Ex nA, Ex nR, Ex ic, Ex pz (plus all Zone 0/1 types)IIC > IIB > IIA
Zone 20 (Dust continuous)Da onlyEx ta, Ex iaD, Ex maDIIIC (Conductive dust) covers IIIB & IIIA
Zone 21 (Dust intermittent)Da or DbEx tb, Ex ibD, Ex mbD, Ex pxDIIIB (Non-conductive dust) covers IIIA (Flyings)
Zone 22 (Dust abnormal)Da, Db, or DcEx tc, Ex icD, Ex pzDIIIC > IIIB > IIIA

IEC 60079-0 Temperature Classes (T1 - T6) for Group II Electrical Equipment (IEC 60079-0 §5.3.2.2)

Temperature ClassMax Surface Temp (°C)Permitted if Gas AIT >Typical Representative Gases / Vapours
T1450 °C> 450 °CHydrogen (560°C), Methane (537°C), Ammonia (630°C), Propane (470°C)
T2300 °C> 300 °CAcetylene (305°C), Ethylene (425°C), Ethanol (363°C), n-Butane (365°C)
T3200 °C> 200 °CPetrol / Gasoline (220-280°C), Diesel / Jet Fuel (210°C), Hydrogen Sulphide (260°C)
T4135 °C> 135 °CAcetaldehyde (140°C), Diethyl Ether (160°C)
T5100 °C> 100 °CSpecial reactive chemical intermediates
T685 °C> 85 °CCarbon Disulphide CS2 (95°C), Ethyl Nitrite (90°C)

→ Launch Module #26 with Interactive Standard Annex Tables