This practical guide shows you how to complete a signed, QR-verified AC Induction Motor & VFD Field Diagnostic Report certificate in OhmCert Module #29 and how to troubleshoot non-compliant readings on site.
1. Step-by-Step OhmCert UI Workflow
- Open Module #29: Navigate to AC Induction Motor & VFD Field Diagnostic Report from the Dashboard.
- Load a 1-Click Standard Annex Preset: Open the blue Standard Annex banner at the top and click a preset (such as "75 kW 400 V Industrial Pump / Compressor VFD Motor (Healthy)") to populate target limits automatically.
- Enter Your Field Measurements: Fill in the measured inputs (Motor Rated Voltage Class (IEEE 43 Table 2), Motor Nameplate Rated Mechanical Power Pn, Motor Nameplate Full-Load Current I_FLC, Measured Terminal Voltage U_L1-L2, Measured Terminal Voltage U_L2-L3, Measured Terminal Voltage U_L3-L1, Measured Motor Phase Current I_L1, Measured Motor Phase Current I_L2, Measured Motor Phase Current I_L3, Winding DC Resistance U1-U2 (or U-V), Winding DC Resistance V1-V2 (or V-W), Winding DC Resistance W1-W2 (or W-U), Temperature-Corrected Stator Insulation R_40C, Max Bearing Housing Temperature (DE / NDE), Measured VFD Shaft-to-Frame Peak Voltage (optional)). Blank inputs stay neutral
PENDING. - Complete the 12-Point Checklist: Grade each item, attach photos if needed, and export the SHA-256 signed PDF certificate.
2. Worked Numerical Field Case Study
Scenario: 75 kW 400 V Industrial Pump / Compressor VFD Motor (Healthy) (IEC 60034 / NEMA MG-1) — LV 75 kW IE3 motor with shaft grounding ring, balanced phases, and 450 MOhm R_40C..
- Motor Rated Voltage Class (IEEE 43 Table 2):
LV Motor (< 1 kV - Min 5 MOhm / Recommended >= 100 MOhm) - Motor Nameplate Rated Mechanical Power Pn:
75 kW - Motor Nameplate Full-Load Current I_FLC:
134 A - Measured Terminal Voltage U_L1-L2:
401 V - Measured Terminal Voltage U_L2-L3:
398 V - Measured Terminal Voltage U_L3-L1:
400 V - Measured Motor Phase Current I_L1:
112 A - Measured Motor Phase Current I_L2:
115 A - Measured Motor Phase Current I_L3:
113 A - Winding DC Resistance U1-U2 (or U-V):
42.4 mOhm - Winding DC Resistance V1-V2 (or V-W):
42.7 mOhm - Winding DC Resistance W1-W2 (or W-U):
42.5 mOhm - Temperature-Corrected Stator Insulation R_40C:
450 MOhm - Max Bearing Housing Temperature (DE / NDE):
64 degC - Measured VFD Shaft-to-Frame Peak Voltage (optional):
2.8 Vpk
3. Engineering Troubleshooting: Corrective Actions When a Reading Fails
- Redistribute single-phase loads or correct upstream loose transformer/breaker lugs to bring motor terminal voltage unbalance below 1.0%.
- Clean and re-torque star/delta terminal links if 4-wire DC winding resistance unbalance exceeds 2.0%.
- Install an AEGIS microfiber shaft grounding ring and/or ceramic-insulated NDE bearing whenever VFD shaft voltage exceeds 5 Vpk.
→ Try This Worked Example Live in Module #29 (Motor & VFD Diagnostics)