#22Raised Floor Signal Reference Grid (SRG) & ESD Grounding Test

Project Framework (report reference): IEC 60364-4-41Applicable Standard: IEEE 1100 (Emerald Book)

Multi-Asset / Multi-Point Equipment Schedule

Inspect multiple transformers, panels, rooms, motors, or RCDs in this module without overwriting previous assets. Each item receives a permanent QR Sticker UID preserved across annual audits.

Sticker UID: OC-SRG0-86E5

Standard Limits, Equations & Space Presets

IEEE Std 1100 Signal Reference Grid (SRG) high-frequency equipotentiality, ANSI/TIA-607-D rack bonding resistance, and ANSI/ESD S20.20 (STM7.1 / STM97.2) static dissipative flooring verification.

One-Click Normative Presets (Auto-fills Target Limits)

Measured Inputs

Calculated / Evaluated Results

ANSI/TIA-607-D requires <= 1 Ohm between bonded points; the point-to-point grid target below 0.1 Ohm is a commissioning convention. ESD floor bands come from ANSI/ESD S20.20 measured to STM7.1.

Pending / Not tested — results stay neutral until valid measured values are entered.

  • Bonding Continuity to Busbar

    - mOhm

    Not tested - enter the measured value. Acceptance: <= 1 Ohm (1000 mOhm) between any two bonded points [ANSI/TIA-607-D]

    Pending
  • Point-to-Point Grid Resistance

    - mOhm

    Not tested - enter the measured value. Acceptance: <= 0.1 Ohm (100 mOhm) across grid nodes [IEEE 1100 commissioning convention]

    Pending
  • High Frequency Impedance at 1 MHz

    - Ohm

    Not tested - enter the measured value. Acceptance: <= 1 Ohm - low HF impedance is what makes the grid a signal reference [IEEE 1100 field convention]

    Pending
  • ESD Floor Resistance to Ground

    - Ohm

    Not tested - < 1E6 Ohm: conductive flooring - acceptable in an ESD protected area when personnel grounding is controlled. [ANSI/ESD S20.20 via STM7.1]

    Pending
  • Walking Body Voltage

    - V

    Not tested - enter the measured value. Acceptance: The flooring and footwear system must keep body voltage below 100 V [ANSI/ESD S20.20 Table 1 (STM97.2)]

    Pending
  • SRG Grid Mesh Spacing

    - m

    Not tested - enter the measured value. Acceptance: Mesh spacing <= 0.60 m (600 x 600 mm raised floor pedestal grid for HF equipotentiality) [IEEE 1100 §8.5 / ANSI-TIA-607-D]

    Pending

Verification Checklist (0 / 13)

Pending
  • 1Signal Reference Grid (SRG) copper strap or round-wire mesh spacing verified <= 0.60 m x 0.60 m (2 ft x 2 ft) across raised floor [IEEE 1100 §8.5]

  • 2Grid intersections exothermically welded, brazed, or clamped with listed low-impedance connectors

  • 3Every 6th raised-floor pedestal (or max 1.8-2.4 m spacing) bonded to the SRG with >= 6 mm2 (#10 AWG) braided/stranded copper jumper

  • 4Every IT server rack, network cabinet, PDU, and CRAH frame bonded to SRG with short, flat braided copper strap (L:W ratio <= 5:1)

  • 5Two-point Ductor / 4-wire Kelvin micro-ohm resistance from rack frame to Telecommunication Grounding Busbar (TGB) verified <= 1000 mOhm (1.0 Ohm) [ANSI/TIA-607-D]

  • 6Point-to-point DC resistance across adjacent SRG grid nodes verified <= 100 mOhm (0.1 Ohm) [IEEE 1100 commissioning target]

  • 7High-frequency impedance across SRG verified <= 1.0 Ohm at 1 MHz to guarantee equipotential plane against fast transients

  • 8Metallic cable trays, basket containment, chilled-water pipes, and fire suppression piping bonded to SRG at regular intervals

  • 9Raised floor tile point-to-ground resistance R_esd measured at 100 V DC (5 lb / 2.27 kg electrode per ANSI/ESD STM7.1) within 1.0E6 to 1.0E9 Ohm dissipative band [ANSI/ESD S20.20]

  • 10Human body voltage generation during walking test (ANSI/ESD STM97.2) verified < 100 V peak across data hall floor

  • 11Technician wrist-strap bonding jacks at server racks verified with 1 MOhm current-limiting series resistor

  • 12Zero isolated ('floating') metallic floor stringers or containment sections found during continuity sweep

  • 13As-built SRG bonding map and ESD tile resistance zone grid archived in facility commissioning register