This practical guide shows you how to complete a signed, QR-verified Raised Floor Signal Reference Grid (SRG) & ESD Grounding Test certificate in OhmCert Module #22 and how to troubleshoot non-compliant readings on site.
1. Step-by-Step OhmCert UI Workflow
- Open Module #22: Navigate to Raised Floor Signal Reference Grid (SRG) & ESD Grounding Test from the Dashboard.
- Load a 1-Click Standard Annex Preset: Open the blue Standard Annex banner at the top and click a preset (such as "600x600 mm Copper-Strip Raised Floor SRG + Dissipative Tile") to populate target limits automatically.
- Enter Your Field Measurements: Fill in the measured inputs (Rack / Frame to Busbar Bonding Resistance, Point-to-Point Grid Resistance, High Frequency Impedance at 1 MHz, ESD Floor Resistance to Ground, Walking Body Voltage (STM97.2), Grid Mesh Size). Blank inputs stay neutral
PENDING. - Complete the 13-Point Checklist: Grade each item, attach photos if needed, and export the SHA-256 signed PDF certificate.
2. Worked Numerical Field Case Study
Scenario: 600x600 mm Copper-Strip Raised Floor SRG + Dissipative Tile (IEEE 1100 / TIA-607-D) — Standard data center raised floor SRG with 2.5E7 Ohm static dissipative tiles..
- Rack / Frame to Busbar Bonding Resistance:
45 mOhm - Point-to-Point Grid Resistance:
18 mOhm - High Frequency Impedance at 1 MHz:
0.35 Ohm - ESD Floor Resistance to Ground:
25000000 Ohm - Walking Body Voltage (STM97.2):
28 V - Grid Mesh Size:
0.60 m
3. Engineering Troubleshooting: Corrective Actions When a Reading Fails
- Replace long round grounding wires between cabinets and the SRG with short (< 0.5 m) flat tinned-copper braided straps.
- Clean and re-torque oxidized pedestal-to-stringer and SRG clamp intersections where node resistance exceeds 100 mOhm.
- Strip insulating floor wax and apply antistatic ESD topical treatment if tile resistance exceeds 1.0E9 Ohm or walking voltage exceeds 100 V.
→ Try This Worked Example Live in Module #22 (SRG & ESD Grounding)